Chapter 10
10-55
Appendices
■
Reference Parameters
Note
Values exceeding the max. output frequency (E1-04 and E3-02) cannot be set. Set the motor
constant parameters first.
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
d1-01
0280
02
80
Frequency reference 1
0 to max.
output
fre-
quency
(See
note.)
0.01 Hz
(Set with
o1-03.)
0.00
Yes
d1-02
0281
02
81
Frequency reference 2
0.00
Yes
d1-03
0282
02
82
Frequency reference 3
0.00
Yes
d1-04
0283
02
83
Frequency reference 4
0.00
Yes
d1-05
0284
02
84
Frequency reference 5
0.00
Yes
d1-06
0285
02
85
Frequency reference 6
0.00
Yes
d1-07
0286
02
86
Frequency reference 7
0.00
Yes
d1-08
0287
02
87
Frequency reference 8
0.00
Yes
d1-09
0288
02
88
Frequency reference 9
0.00
Yes
d1-10
028B
02
8B
Frequency reference 10
0.00
Yes
d1-11
028C
02
8C
Frequency reference 11
0.00
Yes
d1-12
028D
02
8D
Frequency reference 12
0.00
Yes
d1-13
028E
02
8E
Frequency reference 13
0.00
Yes
d1-14
028F
02
8F
Frequency reference 14
0.00
Yes
d1-15
0290
02
90
Frequency reference 15
0.00
Yes
d1-16
0291
02
91
Frequency reference 16
0.00
Yes
d1-17
0292
02
92
Jog frequency reference
6.00
Yes
d2-01
0289
02
89
Frequency reference upper limit
0.0 to
110.0
0.1%
100.0
No
d2-02
028A
02
8A
Frequency reference lower limit
0.0 to
110.0
0.1%
0.0
No
d2-03
0293
02
93
Master speed reference lower limit
0.0 to
110.0
0.1%
0.0
No
d3-01
0294
02
94
Jump frequency 1
0.0 to
400.0
0.1 Hz
0.0
No
d3-02
0295
02
95
Jump frequency 2
0.1 Hz
0.0
No
d3-03
0296
02
96
Jump frequency 3
0.1 Hz
0.0
No
d3-04
0297
02
97
Jump frequency width
0.0 to
20.0
0.1 Hz
1.0
No
d4-01
0298
02
98
Frequency reference hold function
selection
0, 1
1
0
No
d4-02
0299
02
99
+
−
Speed limits
0 to 100
1%
10
No
d6-01
02A0
02
A0
Field weakening level
0 to 100
1%
80
No
d6-02
02A1
02
A1
Field frequency
0.0 to
400.0
0.1 Hz
0.0
No
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...