Chapter 5
5-33
Remote I/O Functions
5-7-2 Control I/O Remote I/O + Unit Status
This remote I/O setting is a default connection path setting, which attaches the 16-bit Unit status data
to the control I/O remote I/O function described in
5-6-1 Control I/O Remote I/O Operation
. This sec-
tion explains the I/O format when the unit status is attached to the control I/O remote I/O.
For details on the function of specific input and output bits/bytes, refer to
5-6-1 Control I/O Remote
I/O Operation
or
5-7-1 Unit Status
.
■
I/O Format (Allocated Words)
●
Outputs (PLC to Inverter)
Instance ID: 101 Decimal (65 Hex)
SYSDRIVE 3G3MV
SYSDRIVE 3G3RV/3G3PV/3G3FV
Byte number
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Wd n
Right-
most
0
Multi-
function
input 7
Multi-
function
input 6
Multi-
function
input 5
Multi-
function
input 4
Multi-
function
input 3
Reverse/
stop
For-
ward/sto
p
Left-
most
1
Multi-
function
output 2
Multi-
function
output 1
Multi-
function
contact
output
Fault
reset
External
fault
input
Wd n+1
Right-
most
2
Frequency reference, rightmost byte
Left-
most
3
Frequency reference, leftmost byte
Wd n+2
Right-
most
4
Left-
most
5
Wd n+3
Right-
most
6
Left-
most
7
Byte number
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Wd n
Right-
most
0
Multi-
function
input 6
Multi-
function
input5
Multi-
function
input4
Multi-
function
input3
Multi-
function
input2
Multi-
function
input1
Reverse/
stop
For-
ward/sto
p
Left-
most
1
Multi-
function
output 2
Multi-
function
output 1
Multi-
function
contact
output
Fault
reset
External
fault
input
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...