Chapter 10
10-52
Appendices
b4-02
01A4
01
A4
Timer function OFF-delay time
0.0 to
3000.0
(See
note 5.)
0.1 s
0.0
No
b5-01
01A5
01
A5
PID control mode selection
0 to 4
1
0
No
b5-02
01A6
01
A6
Proportional gain (P)
0.00 to
25.00
0.01
1.00
Yes
b5-03
01A7
01
A7
Integral (I) time
0.0 to
360.0
0.1 s
1.0
Yes
b5-04
01A8
01
A8
Integral (I) limit
0.0 to
100.0
0.1%
100.0
Yes
b5-05
01A9
01
A9
Derivative (D) time
0.00 to
10.00
0.01 s
0.00
Yes
b5-06
01AA
01
AA
PID limit
0.0 to
100.0
0.1%
100.0
Yes
b5-07
01AB
01
AB
PID offset adjustment
−
100.0 to
100.0
0.1%
0.0
Yes
b5-08
01AC
01
AC
PID primary delay time constant
0.00 to
10.00
0.01 s
0.00
Yes
b5-09
01AD
01
AD
PID output characteristics selection
0, 1
1
0
No
b5-10
01AE
01
AE
PID output gain
0.0 to
25.0
0.1
1.0
No
b5-11
01AF
01
AF
PID reverse output selection
0, 1
1
0
No
b5-12
01B0
01
B0
Selection of PID feedback command
loss detection
0 to 2
1
0
No
b5-13
01B1
01
B1
PID feedback command loss detection
level
0 to 100
1%
0
No
b5-14
01B2
01
B2
PID feedback command loss detection
time
0.0 to
25.5
0.1 s
1.0
No
b5-15
01B3
01
B3
PID sleep function operation level
0.0 to
400.0
0.1 Hz
0.0
No
b5-16
01B4
01
B4
PID sleep operation delay time
0.0 to
25.5
0.1 s
0.0
No
b5-17
01B5
01
B5
Accel/decel time for PID reference
0.0 to
25.5
0.1 s
0.0
No
b6-01
01B6
01
B6
Dwell frequency at start
0.0 to
400.0
0.1 Hz
0.0
No
b6-02
01B7
01
B7
Dwell time at start
0.0 to
10.0
0.1 s
0.0
No
b6-03
01B8
01
B8
Dwell frequency at stop
0.0 to
400.0
0.1 Hz
0.0
No
b6-04
01B9
01
B9
Dwell time at stop
0.0 to
10.0
0.1 s
0.0
No
b8-01
01CC
01
CC
Energy-saving mode selection
0, 1
1
0
No
b8-02
01CD
01
CD
Energy-saving gain
0.0 to
10.0
0.1
0.7 (See
note 2.)
Yes
b8-03
01CE
01
CE
Energy-saving filter time constant
0.0 to
10.0
0.01 s
0.50
(See
note 3.)
Yes
b8-04
01CF
01
CF
Energy-saving coefficient
0.00 to
655.00
(See
note 4.)
0.01
Depends
on
capacity.
No
b8-05
01D0
01
D0
Power detection filter time constant
0 to 2000 1 ms
20
No
b8-06
01D1
01
D1
Search operation voltage limiter
0 to 100
1%
0
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...