Chapter 10
10-20
Appendices
Note 1.
The Net Reference and Reference From Net functions cannot be changed during running.
Note 2.
Under the DeviceNet protocol, the unit for the speed reference is always r/min. The number
of motor poles (2 to 39) must be set in parameter n035/o1-03 (frequency reference setting
and display units) when using DeviceNet (open network). After changing the unit setting,
turn the power OFF and then ON again.
Note 3.
Cannot be changed during running.
01
17
Current scale
Current data unit selection
can be set and read. The
current data unit value is
calculated as follows:
Unit = 0.1 [A] x 1/2
b
b: Current scale set value
Set a negative value as its
2's complement.
−
15 to 15 (F1
to 0F hex)
00
Yes
Yes
Byte
1A
Power scale
Power data unit selection
can be set and read. The
power data unit value is cal-
culated as follows:
Unit = 1 [W] x 1/2
c
c: Power scale set value
Set a negative value as its
2's complement.
−
15 to 15 (F1
to 0F hex)
00
Yes
Yes
Byte
1B
Voltage scale
Voltage data unit selection
can be set and read. The
voltage data unit value is
calculated as follows:
Unit = 1 [V] x 1/2
d
d: Voltage scale set value
Set a negative value as its
2's complement.
−
15 to 15 (F1
to 0F hex)
00
Yes
Yes
Byte
1C
Time scale
Time data unit selection
can be set and read. The
time data unit value is cal-
culated as follows:
Unit = 1 [ms] x 1/2
e
e: Voltage scale set value
Set a negative value as its
2's complement.
−
15 to 15 (F1
to 0F hex)
00
Yes
Yes
Byte
1D
Reference From
Net
00: Reference other than
DeviceNet (n004/b1-01)
01: Operating with
DeviceNet.
---
00
Yes
No
Byte
64
Electric power
Average power value (W)
---
0000
0000
Yes
No
Long
65
Electric power
time scale
Power value measurement
period (T) (reflected when
power is turned ON)
00: 10 minutes
01: 30 minutes
02: 60 minutes
00 to 02
00
Yes
Yes
Byte
6F
Specific alarm
Alarm code of the alarm or
minor fault detected in the
Inverter. For more details,
refer to
8-5 Inverter Alarms
.
---
0000
Yes
No
Word
70
Specific error
Fault code of the fault
detected in the Inverter. For
more details, refer to
8-4
Inverter Faults
.
---
00
Yes
No
Byte
Instance
Attribute
Name
Content
Setting range
Default
Read Write
Size
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...