Chapter 10
10-43
Appendices
10-5-2 Inverter Monitoring Functions (Read)
---
---
000A to 000E
Not used.
00
0F
000F
Reference selection settings
Bit 0
Not used.
Bit 1
PID target value (register 0006H)
1: Enabled 0: Disabled
Bit 2 to 15
Not used.
Class 64
Register
number (hex)
Content
Instance
Attribute
00
20
0020
Inverter status
Bit 0
Operation 1: Operating 0: Stopped
Bit 1
Reverse operation 1: Reverse operation 0: Forward
operation or stopped
Bit 2
Inverter startup complete 1: Completed 0: Not com-
pleted
Bit 3
Error 1: Error
Bit 4
Data setting error 1: Error
Bit 5
Multi-function contact output (terminals M1-M2) 1:
ON 0: OFF
Bit 6
Multi-function PHC output 1 (terminals P1-PC) 1: ON
0: OFF
Bit 7
Multi-function PHC output 2 (terminals P2-PC) 1: ON
0: OFF
Bit 8 to 15
Not used.
00
21
0021
Error details
Bit 0
Overcurrent (OC), ground fault (GF)
Bit 1
Main circuit overvoltage (OV)
Bit 2
Inverter overload (OL2)
Bit 3
Inverter overheat (OH1, OH2)
Bit 4
Injection brake transistor resistance overheat (rr, rH)
Bit 5
Fuse blown (PUF)
Bit 6
PID feedback reference lost (FbL)
Bit 7
External error (EF, EFO)
Bit 8
Hardware error (CPF)
Bit 9
Motor overload (OL1) or overtorque 1 (OL3) detected
Bit 10
PG broken wire detected (PGO), overspeed (OS),
speed deviation (DEV)
Bit 11
Main circuit undervoltage (UV) detected
Bit 12
Main circuit undervoltage (UV1), control power sup-
ply error (UV2), inrush prevention circuit error (UV3)
Bit 13
Missing output phase (LF)
Bit 14
RS-422A/485 communications error (CE)
Bit 15
Operator disconnected (OPR)
Class 64
Register
number (hex)
Content
Instance
Attribute
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...