Chapter 4
4-2
SYSDRIVE Inverter Settings
4-1
SYSDRIVE 3G3MV Settings
In order to perform DeviceNet communications, it is necessary to make settings for the Inverter
according to the application.
Note
The parameters set here are applied to the DeviceNet Communications Unit when the power is
turned ON. Turn OFF the power after changing parameters and turn ON again to apply them.
4-1-1 Run Command Selection
Perform the above setting according to the source of the run commands (forward operation, reverse
operation, STOP) in the application. When run commands (forward operation, reverse operation,
STOP) are always to be made from DeviceNet communications, set to “3."
■
Switching of Run Commands from DeviceNet Communications
There is a switching signal, “Net. Ctrl.,” for run commands from the standard remote I/O of the
DeviceNet Communications Unit. The input method for run commands can be changed in the follow-
ing way using the “Net. Ctrl.” signal.
Net. Ctrl. = 1 (ON)
Enables run commands from DeviceNet communications (remote I/O run commands become valid)
regardless of the setting in n003.
Con-
stant
Register
number
(hex)
Name
Content
Setting
range
Setting
unit
Default
setting
Write
during
operation
n003
0103
Run com-
mand source
selection
Selects the run/stop command
input method for the Inverter.
(Becomes valid when the
Remote mode is selected from
Local/Remote.)
0: Run/stop commands from
the Digital Operator are valid.
1: Terminal block (multi-func-
tion input) run commands are
valid.
2: RS-422/485 communica-
tions run commands are valid.
3: Run commands from the
Optional Unit (DeviceNet Com-
munications Unit) are valid.
Note
In Local mode, run com-
mands are restricted to
those performed using
the operation keys of the
Digital Operator.
0, 1, 2,
3
1
0
No
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...