Chapter 10
10-7
Appendices
■
Object Details
Note 1.
The setting ranges are the same as the respective remote I/O setting ranges.
Note 2.
The remote I/O functions are the same as the functions explained in
Chapter 5 Remote I/O
Functions
.
Note 3.
Remote I/O can be performed by means of message communications. When a normal re-
mote I/O communications connection is established, however, the message communica-
tions cannot be used for that purpose. Even if an attempt is made to use message
communications, they will be overwritten by remote I/O inputs.
10-2-5 DeviceNet Connection Objects: Class 05 Hex
DeviceNet connection objects are objects related to information and operations involving DeviceNet
communications connections. The Master Unit uses the information and operations of these objects
to execute the initial processing for communications.
The functions and data have no particular use for the user.
Use this object when switching the remote I/O function.
Instance
Attribute
Name
Content
Setting range
Default
Read
Write
Size
14
03
Remote I/O data Operation is the same as
for basic remote I/O (out-
put).
See note 1.
00 00 00
00
Yes
Yes
Byte
×
4
15
03
Remote I/O data Operation is the same as
for standard remote I/O
(output).
See note 1.
00 00 00
00
Yes
Yes
Byte
×
4
46
03
Remote I/O data Operation is the same as
for basic remote I/O
(input).
---
00 00 00
00
Yes
No
Byte
×
4
47
03
Remote I/O data Operation is the same as
for standard remote I/O
(input).
---
00 00 00
00
Yes
No
Byte
×
4
64
03
Remote I/O data Operation is the same as
for special remote I/O
(output).
See note 1.
00 00 00
00 00
Yes
Yes
Byte
×
5
65
03
Remote I/O data Remote I/O data
See note 1.
00 00 00
00 00 00
00 00
Yes
Yes
Byte
×
8
96
03
Remote I/O data Operation is the same as
for special remote I/O
(input).
---
00 00 00
00 00
Yes
No
Byte
×
5
97
03
Remote I/O data Operation is the same as
for control remote I/O
(input).
---
00 00 00
00 00 00
00 00
Yes
No
Byte
×
8
98
03
Remote I/O data Operation is the same as
for control remote I/O +
unit status (input).
---
00 00 00
00 00 00
00 00 00
00
Yes
No
Byte
×
10
99
03
Remote I/O data Operation is the same as
for control remote I/O +
multi-function input moni-
tor (input).
---
00 00 00
00 00 00
00 00 00
Yes
No
Byte
×
9
9A
03
Remote I/O data Operation is the same as
for unit status (input).
---
00 00
Yes
No
Byte
×
2
9B
03
Remote I/O data Operation is the same as
for multi-function input
monitor (input).
---
00
Yes
No
Byte
×
1
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...