Chapter 10
10-10
Appendices
Note 1.
“Produced” means output (Inverter to PLC), and “Consumed” means input (PLC to Inverter).
Note 2.
Instance 02 is a Poll connection, Instance 03 is a Bit-strobe connection, and Instance 04 is
a COS or Cyclic connection.
Note 3.
The following table shows the connection path for each Instance.
●
Produced Connection Path
02
03
04
Remote
I/O
(See
note 2.)
08
Consumed con-
nection size
Indicates the maximum
number of bytes for recep-
tion.
---
See note
3.
Yes
No
Word
09
Expected packet
rate
Indicates the length of the
internal processing time-
out when a communica-
tions request is received.
Incremented by 10-ms
units.
0 to 65,535
(ms)
0000
(0 ms)
Yes
Yes
Word
0C
Watchdog time-
out action
Indicates the action for
internal processing time-
out related to communica-
tions.
00: Retain timeout status
(until reset or cleared).
---
00
Yes
No
Byte
0D
Produced con-
nection path
length
Indicates number of bytes
of data for produced con-
nection path.
---
See note
3.
Yes
No
Word
0E
Produced con-
nection path
Indicates the data for
defining the application
object for sending this
object (instance).
* Has a function for
switching the DeviceNet
Communication Unit/
Card’s remote I/O oper-
ation.
---
See note
3.
Yes
No
Array
0F
Consumed con-
nection path
length
Indicates the number of
bytes of data for the con-
sumed connection path.
---
See note
3.
Yes
No
Word
10
Consumed con-
nection path
Indicates the data for
defining the application
object for receiving this
object (instance).
* Has a function for
switching the DeviceNet
Communication Unit/
Card's remote I/O oper-
ation.
---
See note
3.
Yes
No
Array
Remote I/O function
Connection
Size
Path
Length
Connection Path
Remarks
46 hex: Basic remote I/O (input)
0004
0006
20 04 24 46 30 03
---
47 hex: Standard remote I/O
(input)
0004
0006
20 04 24 47 30 03
Instance 02
default setting
96 hex: Special remote I/O (input)
0005
0006
20 04 24 96 30 03
---
97 hex: Control I/O remote I/O
(input)
0008
0006
20 04 24 97 30 03
---
Instance
Attribute
Name
Content
Setting range
Default
Read
Write
Size
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...