Chapter 10
10-102
Appendices
Note 1.
Values in parentheses are for 400-V-class Inverters.
Note 2.
The default setting depends upon the type of Inverter. The value for a 200-V-class 0.4-kW
Inverter is given above.
■
Operator Parameters
Note
The default setting depends upon the type of Inverter. The value for a 200-V-class 0.4-kW
Inverter is given above.
L8-05
04A8
01
BC
Input open-phase protection selection
0, 1
1
0
No
L8-07
04AA
01
BD
Output open-phase protection selec-
tion
0, 1
1
0
No
L8-10
04AD
01
BE
Ground fault protection operation
selection
0, 1
1
1
No
L8-17
04B4
---
---
Low-speed carrier frequency reduction
selection (2)
0 to 3
1
1
No
L8-19
04B6
---
---
Low-speed Inverter overload (OL2)
characteristic selection
0, 1
1
0
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
o1-01
0500
01
BF
Monitor selection
4 to 38
1
6
Yes
o1-02
0501
01
C0
Monitor selection after power-on
1 to 4
1
1
Yes
o1-03
0502
01
C1
Frequency reference setting and dis-
play units
0 to
39999
1
0
No
o1-04
0503
01
C2
V/f pattern setting units
0, 1
1
0
No
o1-05
0504
01
C3
Not used.
---
---
0
---
o2-01
0505
01
C4
Local/Remote Key
0, 1
1
1
No
o2-02
0506
01
C5
Stop Key
0, 1
1
1
No
o2-03
0507
---
---
User constant initial values
0 to 2
1
0
No
o2-04
0508
01
C6
Inverter capacity selection
0 to FF
(See
note.)
1
0 (See
note.)
No
o2-05
0509
01
C7
Frequency reference setting method
0, 1
1
0
No
o2-06
050A
01
C8
Operation selection when Digital Oper-
ator is disconnected
0, 1
1
0
No
o2-07
050B
---
---
Cumulative operation time setting
0 to
65535
1 hr
0
No
o2-08
050C
---
---
Cumulative operation time selection
0, 1
1
0
No
o2-09
050D
01
C9
Factory use
---
---
1
---
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...