Chapter 10
10-60
Appendices
H2-02
040C
04
0C
Terminal P1 function select (open col-
lector)
0 to 37
1
1
No
H2-03
040D
04
0D
Terminal P2 function select (open col-
lector)
0 to 37
1
2
No
H3-01
0410
04
10
Signal select terminal A1 (voltage)
(See note 4.)
0 or 1
1
0
No
H3-02
0411
04
11
Frequency reference (voltage)
gain (terminal A1)
0.0 to
1000.0
0.1%
100.0
Yes
H3-03
0412
04
12
Frequency reference (voltage)
bias (terminal A1)
−
100.0 to
100.0
0.1%
0.0
Yes
H3-08
0417
04
17
Multi-function analog input terminal A2
signal level selection
0 to 2
1
2
No
H3-09
0418
04
18
Multi-function analog input terminal A2
function selection
0 to 1F
1
0
No
H3-10
0419
04
19
Frequency reference (current)
gain (terminal A2)
0.0 to
1000.0
0.1%
100.0
Yes
H3-11
041A
04
1A
Frequency reference (current)
bias (terminal A2)
−
100.0 to
100.0
0.1%
0.0
Yes
H3-12
041B
04
1B
Analog input filter time constant
0.00 to
2.00
0.01 s
0.00
No
H3-13
041C
04
1C
Terminal A1/A2 switching
0, 1
1
0
No
H4-01
041D
04
1D
Multi-function analog output 1 monitor
selection (terminal FM)
1 to 40
1
2
No
H4-02
041E
04
1E
Multi-function analog output 1gain (ter-
minal FM)
0.0 to
1000.0
(0.00 to
2.50)
(see
note 3.)
0.1%
(0.01)
(See
note 3.)
100.0
(1.00)
(See
note 3.)
Yes
H4-03
041F
04
1F
Multi-function analog output 1 bias (ter-
minal FM)
−
110.0 to
110.0
(
−
10.0 to
10.0)
(See
note 3.)
0.1%
0.0
Yes
H4-04
0420
04
20
Multi-function analog output 2 monitor
selection (terminal AM)
1 to 40
1
3
No
H4-05
0421
04
21
Multi-function analog output 2 gain (ter-
minal AM)
0.0 to
1000.0
(0.00 to
2.50)
0.1%
(0.01)
(See
note 3.)
50 (0.50)
(See
note 3.)
Yes
H4-06
0422
04
22
Multi-function analog output 2
bias (terminal AM)
−
110.0 to
110.0
(
−
10.0 to
10.0)
(See
note 3)
0.1%
0.0
Yes
H4-07
0423
04
23
Multi-function analog output 1 signal
level selection
0, 1, 2
(0, 1)
(See
note 3.)
1
0
No
H4-08
0424
04
24
Multi-function analog output 2 signal
level selection
0, 1
1
0
No
H5-01
0425
04
25
Slave address
0 to 20
(See
note 2.)
1
1F
No
H5-02
0426
04
26
Communication speed selection
0 to 4
1
3
No
H5-03
0427
04
27
Communication parity selection
0 to 2
1
0
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...