![background image](http://html1.mh-extra.com/html/omron/3g3mv-pdrt2/3g3mv-pdrt2_user-manual_743559356.webp)
Chapter 10
10-98
Appendices
Note 1.
Values in parentheses are for 400-V-class Inverters.
Note 2.
When the control mode is changed, the Inverter will revert to default settings. (The open loop
vector control default settings are given above.)
Note 3.
The default setting depends upon the type of Inverter. The value for a 200-V-class 0.4-kW
Inverter is given above.
Note 4.
The setting range is 10% to 200% of the Inverter's rated output current. The values for a 200-
V-class 0.4-kW Inverter are given above.
Note 5.
The setting range is 0.00 to (motor's rated current -0.1 A). The value for a 200-V-class 0.4-
kW Inverter is given above.
■
Option Parameters
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
F1-01
0380
01
70
Number of PG pulses
0 to
60000
1 p/r
1000
No
F1-02
0381
01
71
PG disconnection stopping method
(PGO)
0 to 3
1
1
No
F1-03
0382
01
72
PG overspeed stopping method
0 to 3
1
1
No
F1-04
0383
01
73
PG speed deviation stopping method
0 to 3
1
3
No
F1-05
0384
01
74
PG rotation setting
0, 1
1
0
No
F1-06
0385
01
75
PG output ratio
0 to 132
1
1
No
F1-07
0386
01
76
Selecting integral control during accel/
decel.
0, 1
1
0
No
F1-08
0387
01
77
Overspeed (OS) detection level.
0 to 120
1%
115
No
F1-09
0388
01
78
Overspeed (OS) detection time
0.0 to 2.0 0.1 s
0.0 (See
note 1.)
No
F1-10
0389
01
79
PG speed deviation detection level
(DEV)
0 to 50
1%
10
No
F1-11
038A
01
7A
PG speed deviation detection time
(DEV)
0.0 to
10.0
0.1 s
0.5
No
F1-12
038B
01
7B
Number of PG gear teeth 1
0 to 1000 1
0
No
F1-13
038C
01
7C
Number of PG gear teeth 2
0 to 1000 1
0
No
F1-14
0397
01
7D
PG disconnection detection time
0.0 to
10.0
0.1 s
2.0
No
F2-01
038D
---
---
Analog Reference Card selection
0, 1
1
0
No
F3-01
038E
---
---
Digital Reference Card input selection
0 to 7
1
0
No
F4-01
038F
---
---
Channel 1 output monitor selection
1 to 38
(See
note 2.)
1
2
No
F4-02
0390
---
---
Channel 1 gain
0.00 to
2.50
0.01
1.00
Yes
F4-03
0391
---
---
Channel 2 output monitor selection
1 to 38
(See
note 2.)
1
3
No
F4-04
0392
---
---
Channel 2 gain
0.00 to
2.50
0.01
0.50
Yes
F4-05
03A0
---
---
Channel 1 bias
−
10.0 to
10.0
0.1%
0.0
Yes
F4-06
03A1
---
---
Channel 2 bias
−
10.0 to
10.0
0.1%
0.0
Yes
F5-01
0393
---
---
Not used.
---
---
0
---
F5-02
0394
---
---
Not used.
---
---
1
---
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...