Control Supervisor Objects: Class 29 Hex
Control supervisor objects are objects that have Inverter control I/O-related functions. They are
assigned according to their particular control I/O functions, such as forward operation, reverse oper-
ation, error detection, and so on. Be careful when setting up a remote I/O communications connec-
tion. These functions are shared with similar functions used for remote I/O, so even if they have been
set for message operations they may get rewritten for remote I/O.
■
Support Service Codes
■
Object Details
Service code number (hex)
Service
0E
Get attribute single
10
Set attribute single
05
Reset attribute: Can be sent to Class 29/Instance 01.
Turns OFF the Forward Operation and Reverse Operation inputs and turns
ON the Fault Reset. Then turns OFF the Fault Reset when Inverter Ready is
output.
Instance
Attribute
Name
Content
Setting range
Default
Read
Write
Size
00
01
Object Software
Revision
Indicates class 29 soft-
ware revisions. The revi-
sion value is advanced
whenever there is a
change.
---
0001
Yes
No
Word
01
03
Forward/Stop
00: Stop
01: Forward operation
00, 01
00
Yes
Yes
Byte
04
Reverse/Stop
00: Stop
01: Reverse operation
00, 01
00
Yes
Yes
Byte
05
Net Control
Local/remote
switch
(See note 1.)
00: Operate with setting in
n003/b1-02.
01: Operate by DeviceNet
(not valid with 3G3FV)
00, 01
00
Yes
Yes
Byte
06
State
Inverter status
(See note 1.)
00 hex: Vendor specific
01 hex: Startup
02 hex: Not Ready
03 hex: ready
04 hex: Enabled
05 hex: Stopping
06 hex: Fault_Stop
07 hex: Faulted
---
03
Yes
No
Byte
07
During forward
run
00: No Inverter output or
operating in reverse.
01: Forward operation or
DC braking
(Either DC braking from
reverse operation or oper-
ating forward.)
---
00
Yes
No
Byte
08
During reverse
run
00: No Inverter output or
operating in forward.
01: Operating in reverse
(reverse operation output
status)
Becomes “00” with DC
braking.
---
00
Yes
No
Byte
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...