Chapter 10
10-59
Appendices
Note
Values in parentheses are Asian model Inverters
■
External Terminal Function Parameters
F1-12
038B
03
8B
Number of PG gear teeth 1
0 to 1000 1
0
No
F1-13
038C
03
8C
Number of PG gear teeth 2
0 to 1000 1
0
No
F1-14
038D
03
8D
PG open-circuit detection time
0.0 to
10.0
0.1 s
2.0
No
F4-01
0391
03
91
Channel 1 monitor selection
1 to 40
1
2
No
F4-02
0392
03
92
Channel 1 gain
0.00 to
2.50
0.01
1.00
Yes
F4-03
0393
03
93
Channel 2 monitor selection
1 to 40
1
3
No
F4-04
0394
03
94
Channel 2 gain
0.00 to
2.50
0.01
0.50
Yes
F4-05
0395
03
95
Channel 1 output monitor bias
−
10.0 to
10.0
0.1
0.0
Yes
F4-06
0396
03
96
Channel 2 output monitor bias
−
10.0 to
10.0
0.1
0.0
Yes
F4-07
0397
03
97
Analog output signal level for channel 1 0, 1
1
0
No
F4-08
0398
03
98
Analog output signal level for channel 2 0, 1
1
0
No
F5-01
0399
03
99
Not used.
---
---
0
No
F5-02
039A
03
9A
Not used.
---
---
1
No
F5-03
039B
03
9B
Not used.
---
---
2
No
F5-04
039C
03
9C
Not used.
---
---
4
No
F5-05
039D
03
9D
Not used.
---
---
6
No
F5-06
039E
03
9E
Not used.
---
---
37
No
F5-07
039F
03
9F
Not used.
---
---
0F
No
F5-08
03A0
03
A0
Not used.
---
---
0F
No
F5-09
03A1
03
A1
Not used.
---
---
0
No
F6-01
03A2
03
A2
DeviceNet fault operation selection
0 to 3
1
1
No
F6-02
03A3
03
A3
Communications external fault input
detection method selection
0, 1
1
0
No
F6-03
03A4
03
A4
Communications external fault input
operation selection
0 to 3
1
1
No
F6-04
03A5
03
A5
Not used.
---
---
0
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
H1-01
0400
04
00
Terminal S3 function selection
0 to 68
1
24
No
H1-02
0401
04
01
Terminal S4 function selection
0 to 68
1
14
No
H1-03
0402
04
02
Terminal S5 function selection
0 to 68
1
3 (0)
(See
note 1.)
No
H1-04
0403
04
03
Terminal S6 function selection
0 to 68
1
4 (3)
(See
note 1.)
No
H1-05
0404
04
04
Terminal S7 function selection
0 to 68
1
6 (4)
(See
note 1.)
No
H2-01
040B
04
0B
Terminal M1-M2 Select
0 to 37
1
0
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...