Chapter 2
2-6
Example System Startup
2-3
Setting and Wiring Hardware
Use the following procedures to mount, set, and wire the hardware.
2-3-1 Mounting and Setting the DeviceNet (Master) Unit
■
Settings
The components, functions, and switch settings for the CS1W-DRM21(-V1) or CJ1W-DRM21
DeviceNet (Master) Unit mounted to a CS/CJ-series PLC are shown as an example in the following
diagram.
For information on switch settings, refer to the operation manual for the DeviceNet (Master) Unit.
■
CS1W-DRM21(-V1)
UNIT
No.
NODE
ADR
ON
DRM21
CS
MS
NS
4
3
2
1
DR0
DR1
ESTP
HOLD
X10
1
987
654
32
10
X10
0
987
654
32
10
FEDC
BA987
654
3210
1234
Indicators
Unit No. switch
This rotary switch sets the single-digit hexadecimal
unit number of the Master on the DeviceNet network.
Node address switches
These rotary switches set the double-digit decimal
node address of the Unit.
DIP switch
These pins have the following functions:
Pins 1 and 2: Baud rate
Pins 3:
Continue/stop remote I/O communications
for error (for Master functions)
Pin 4:
Hold/clear I/O for communications error
(for Slave functions).
Communications connector
This connector is connected to the Network
communications cable. Communications power is
also supplied through this connector. An XW4B-
05C1-H1-D Parallel Connector with Screws is
provided as the node connector.
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...