Chapter 8
8-12
Communications Errors
8-5
Inverter Alarms
■
Detecting Inverter Alarms
The Inverter’s alarm codes are not specified in DeviceNet, they are a proprietary function of these
products. When an alarm occurs, the status will change as described below.
■
Reading the Alarm Code
The following methods can be used to read the Inverter’s alarm code.
■
Alarm Codes
The following table lists the alarm codes. Refer to the Maintenance Operation Chapter of your
Inverter User’s Manual for more details on troubleshooting and correcting alarms (also known as
warnings and non-fatal faults).
●
3G3MV Alarm Codes
Function
Inverter alarm status
Remote I/O
The alarm output allocated in the remote I/O will turn ON.
If necessary, we recommend programming a sequence to handle the alarm (such as
stopping the Inverter) when the alarm output goes ON.
Explicit messages
Read the alarm output for Class 29, Instance 1, Attribute 0B using message commu-
nications. We recommend programming a stop sequence (such as turning OFF all
related inputs controlling the Inverter) when an alarm occurs in the Inverter.
Function
Inverter alarm status
Inverter’s Operator dis-
play
When the Inverter is in alarm status, the relevant information will be displayed (flash-
ing) on the Inverter’s Digital Operator.
Explicit messages
The alarm code of an alarm that is currently occurring can be read with message
communications.
DeviceNet Communications Unit/Card alarm code: Class 2A, Instance 1, Attribute 6F
Alarm code (hex)
Operator display
Meaning
0000
---
No Inverter alarm detected
8000
STP (flashing)
Operator stopped
8001
SER (flashing)
Sequence error
8002
EF (flashing)
External terminal fault
8003
BB (flashing)
Baseblock input
8004
OL3 (flashing)
Overtorque 1
8005
OH (flashing)
Cooling fins overheating
8006
OV (flashing)
Main circuit overvoltage
8007
UV (flashing)
Main circuit undervoltage
8008
FAN (flashing)
Cooling fan fault
8009
CE (flashing)
Communications timeout
800A
BUS (flashing)
Option transfer error
800C
OH3 (flashing)
Motor overheating
800D
FBL (flashing)
Feedback loss error
800E
STP (flashing)
Emergency stop
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...