Chapter 5
5-7
Remote I/O Functions
4.Click the
Connection
Tab of the
Advanced Setting
Window and select
User Setup
.
5.Select
Use Poll Connection
and
Use COS connection
.
6.Set
Extended Control Status
(Control I/O remote I/O) for the IN data and
Extended Control Com-
mand
(Control I/O remote I/O) for the OUT data as the poll connection’s connection paths.
7.Set
Unit Status
for the IN data as the COS connection’s connection path.
Note
When a CS/CJ-series DeviceNet (Master) Unit is being used, set the COS connection’s OUT
data to the same setting set for the poll connection’s OUT data. If the connection paths do not
match, it will not be possible to select both
Use Poll Connection
and
Use COS Connection
.
Reference
The following connection path settings will be allocated automatically if you select the connection but
leave the connection path settings blank.
8.Click the
OK
Button to close the
Advanced Settings
Window.
Connection
OUT (PLC
→
Inverter)
IN (PLC
←
Inverter)
Poll
Slave’s default connection path setting
Slave’s default connection path setting
Bit-strobe
Not allocated.
Slave’s default connection path setting
COS
Not allocated.
Unit Status 154 decimal (9A hex)
Cyclic
Not allocated.
Unit Status 154 decimal (9A hex)
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...