![background image](http://html1.mh-extra.com/html/omron/3g3mv-pdrt2/3g3mv-pdrt2_user-manual_743559297.webp)
Chapter 10
10-39
Appendices
■
Function Group 4 (n120 to n179)
n108
016C
01
6C
Motor leakage inductance
0.00 to
655.0
0.01 mH
Differs
with
capacity.
No
n109
016D
01
6D
Torque compensation limit
0 to 250
1%
150
No
n110
016E
01
6E
Motor no-load current
0 to 99
1%
Differs
with
capacity.
No
n111
016F
01
6F
Slip compensation gain
0.0 to 2.5 0.1
0.0
Yes
n112
0170
01
70
Slip compensation primary delay time
0.0 to
25.5
0.1 s
2.0
No
n113
0171
01
71
Slip compensation during regeneration 0, 1
1
0
No
n114
---
---
---
Not used.
---
---
---
---
n115
0173
01
73
Stall prevention level automatic sup-
pression selection
0, 1
1
0
No
n116
0174
01
74
Stall prevention acceleration/decelera-
tion time setting
0, 1
1
0
No
n117
0175
01
75
Low torque detection selection
0 to 4
1
0
No
n118
0176
01
76
Low torque detection level
0 to 200
1%
10
No
n119
0177
01
77
Low torque detection time
0.1 to
10.0
0.1 s
0.1
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
n120
0178
01
78
Frequency reference 9
0.00 to
maxi-
mum fre-
quency
0.01 Hz
(set with
n035)
0.00
Yes
n121
0179
01
79
Frequency reference 10
0.00
Yes
n122
017A
01
7A
Frequency reference 11
0.00
Yes
n123
017B
01
7B
Frequency reference 12
0.00
Yes
n124
017C
01
7C
Frequency reference 13
0.00
Yes
n125
017D
01
7D
Frequency reference 14
0.00
Yes
n126
017E
01
7E
Frequency reference 15
0.00
Yes
n127
017F
01
7F
Frequency reference 16
0.00
Yes
n128
01D3
01
D3
PID control selection
0 to 8
1
0
No
n129
01D4
01
D4
Feedback value adjustment gain
0.00 to
10.00
0.01
1.00
Yes
n130
0182
01
82
Proportional gain (P)
0.0 to
25.0
0.1
1.0
Yes
n131
0183
01
83
Integral time (I)
0.0 to
360.0
0.1 s
1.0
Yes
n132
0184
01
84
Derivative time (D)
0.00 to
2.50
0.01 s
0.00
Yes
n133
0185
01
85
PID offset adjustment
−
100 to
100
1%
0
Yes
n134
0186
01
86
Integral (I) upper limit
0 to 100
1%
100
Yes
n135
0187
01
87
PID primary delay time
0.0 to
10.0
0.1 s
0.0
Yes
n136
0188
01
88
Feedback loss detection selection
0 to 2
1
0
No
n137
0189
01
89
Feedback loss detection level
0 to 100
1%
0
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...