Chapter 10
10-16
Appendices
Note 1.
The following table shows the status of remote I/O output signals and operation indicated by
the content of Attribute 06 (State, i.e., Inverter status).
Note 2.
The Net Control and Control From Net functions cannot be changed during running.
Note 3.
A DeviceNet Fault mode can be set from communications in the 3G3MV only; it cannot be
changed from communications in the 3G3RV or 3G3FV. Set the fault mode in the Inverter’s
parameters.
●
Fault Codes
01
11
Force Fault/Trip
Communica-
tions external
fault input
00: Normal operation
01: Communications
external fault input
00, 01
00
Yes
Yes
Byte
12
Force Status
Communica-
tions external
fault input status
00: Normal status
01: Communications
external fault detected.
(Inverter stopped with fault
detection.)
---
00
Yes
No
Byte
Setting
Status
Condition
00 hex
Vendor specific
A condition other than the ones
below.
01 hex
Startup: Preparation not complete (setting con-
stants)
Inverter Ready signal is OFF.
02 hex
Not ready: Stopped (preparation complete)
Inverter Ready signal is ON and Dur-
ing Run signal is OFF.
03 hex
Inverter ready: Stopped (preparation complete) Inverter Ready signal is ON and Dur-
ing Run signal is OFF.
04 hex
Enabled: Operating
During Run signal (control I/O) is
ON.
05 hex
Stopping: Decelerating (Operating with both for-
ward and reverse references equal to 0.)
Ctrl. From Net is ON, During Forward
Run is OFF, During Reverse Run is
OFF, and During Run is ON.
06 hex
Fault_Stop: Operating with fault detected
Alarm signal is ON.
07 hex
Faulted: Fault detected
Fault signal is ON.
DeviceNet error code
Operator display
Meaning
0000
---
Inverter normal
2120
GF
Ground fault
2130
SC
Short circuit
2200
OL2
Inverter overload
2220
OL1
Motor overload
2221
OL3
Overtorque detection 1
2222
OL4
Overtorque detection 2
2300
OC
Overcurrent
3130
PF
Input phase loss
LF
Output phase loss
3210
OV
Main circuit overvoltage
3220
UV1
Undervoltage (main)
3222
UV3
Undervoltage (MC)
4200
OH
Overheat
Instance
Attribute
Name
Content
Setting range
Default
Read Write
Size
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...