Chapter 6
6-11
Message Communications
Note 1.
The following table shows the status of remote I/O output signals and operation indicated by
the content of Attribute 06 (State, i.e., Inverter status).
Note 2.
The Net Control and Control From Net functions cannot be changed during running.
01
09
Inverter Ready
00: Preparing
Initial processing/ not
drive mode/ fault
01: Inverter ready
Inverter can receive run
command.
---
00
Yes
No
Byte
0A
Fault
00: Normal
01: Fault
---
00
Yes
No
Byte
0B
Alarm (minor
fault)
00: Normal
01: Alarm (minor fault)
---
00
Yes
No
Byte
0C
Fault Reset
00: Normal status
01: Fault reset
00, 01
00
Yes
Yes
Byte
0D
Fault code
Indicates the contents of
fault that occur. (See the
fault code list on the fol-
lowing page.)
---
0000
Yes
No
Word
0F
Control From
Net
Run signal input
status
(See note 2.)
00: Operating with an
n003/b1-02 setting other
than DeviceNet.
01: Operating by
DeviceNet.
---
00
Yes
No
Byte
10
DeviceNet Fault
mode
(See note 3.)
00: Stop operation.
01: Continue operation.
02: Maker's specifications
3G3MV: 00,
01
3G3RV: ---
3G3FV: ---
3G3MV:
00
3G3RV:
02
3G3FV:
02
Yes
Yes
Byte
11
Force Fault/Trip
Communica-
tions external
fault input
00: Normal operation
01: Communications
external fault input
00, 01
00
Yes
Yes
Byte
12
Force Status
Communica-
tions external
fault input status
00: Normal status
01: Communications
external fault detected.
(Inverter stopped with fault
detection.)
---
00
Yes
No
Byte
Setting
Status
Condition
00 hex
Vendor specific
A condition other than the ones
below.
01 hex
Startup: Preparation not complete (setting con-
stants)
Inverter Ready signal is OFF.
02 hex
Not ready: Stopped (preparation complete)
Inverter Ready signal is ON and Dur-
ing Run signal is OFF.
03 hex
Inverter ready: Stopped (preparation complete) Inverter Ready signal is ON and Dur-
ing Run signal is OFF.
04 hex
Enabled: Operating
During Run signal (control I/O) is
ON.
05 hex
Stopping: Decelerating (Operating with both
forward and reverse references equal to 0.)
Ctrl. From Net is ON, During For-
ward Run is OFF, During Reverse
Run is OFF, and During Run is ON.
06 hex
Fault_Stop: Operating with fault detected
Alarm signal is ON.
07 hex
Faulted: Fault detected
Fault signal is ON.
Instance
Attribute
Name
Content
Setting range
Default
Read
Write
Size
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...