Chapter 4
4-8
SYSDRIVE Inverter Settings
4-2-3 DeviceNet Communications Settings
The parameters below are for functions that are exclusive to DeviceNet communications. Set these
parameters according to the desired application.
Note
If F6-01 is set to 3 (continues operating), the Inverter will continue operating when a communi-
cations fault occurs according to the contents of settings immediately before. Be sure to take
any steps necessary to ensure safety, such as installing a limit switch or an emergency stop
switch.
Parameter
No.
Name
Contents
Setting
range
Default
setting
Operator display
F6-01
Communications fault opera-
tion
Select the Inverter operation per-
formed when a communications
fault is detected.
0: Decelerates to a stop using C1-
02 deceleration time/fault detec-
tion
1: Coasts to a stop/fault detection
2: Decelerates to a stop using the
C1-09 emergency stop time/
fault detection
3: Continues operating/alarm
detection (See note.)
0 to 3
1
Comm Bus Flt Sel
F6-02
Communications external fault
input: detection method
Select the detection method used
for the communications external
fault input from communications
(DeviceNet Communications
Card).
0: Faults always detected.
1: Faults detected only while run-
ning (i.e., when Run Com-
mands are input)
0, 1
0
EFO Detection
F6-03
Communications external fault
input: operation
Select the Inverter operation per-
formed when there is a communi-
cations external fault (EFO) input
from communications (DeviceNet
Communications Card).
0: Decelerates to a stop using C1-
02 deceleration time/fault detec-
tion
1: Coats to a stop/fault detection
2: Decelerates to a stop using the
C1-09 emergency stop time/
fault detection
3: Continues operating/alarm
detection
0 to 3
1
EFO Fault Action
F6-04
Not used
Do not set.
---
0
Trace Sample Tim
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...