Chapter 10
10-35
Appendices
●
Communications Error Content: Register Number 003D Hex
10-4-3 Parameter Reading and Writing
The following tables show the SYSDRIVE 3G3MV Inverter parameter classes, instances and
attributes, and the corresponding register numbers. Write and read the various parameters with “1"
as the minimum setting unit. Negative numbers are expressed as two's complements. When param-
eters are written, the settings for parameters that can be written during operation become valid after
the being set in RAM, whereas the settings for parameters that cannot be written during operation,
become valid from the next operation. Send an enter command to save the set data in EEPROM.
Note
The 2 register numbers that are different from RS-422/485 communications are indicated by
shading (refer to page 10-39).
■
Function Group 1 (n001 to n049)
Note
[ ] values indicate those for 400-V-class Inverters.
Bit
Content
0
CRC error (1: error)
1
Incorrect data length (1: error)
2
Not used.
3
Parity error (1: error)
4
Overrun error (1: error)
5
Framing error (1: error)
6
Communications timeover (1: error)
7 to 15
Not used.
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
n001
0101
01
01
Parameter write-prohibit selection/
parameter initialization
0 to 9
1
1
No
n002
0102
01
02
Control mode selection
0, 1
1
0
No
n003
0103
01
03
Run command selection
0 to 3
1
0
No
n004
0104
01
04
Frequency reference selection
0 to 9
1
0
No
n005
0105
01
05
Stopping method selection
0, 1
1
0
No
n006
0106
01
06
Reverse rotation-prohibit selection
0, 1
1
0
No
n007
0107
01
07
STOP Key function selection
0, 1
1
0
No
n008
0108
01
08
Frequency reference selection in local
mode
0, 1
1
0
No
n009
0109
01
09
Operator frequency setting method
selection
0, 1
1
0
No
n010
010A
01
0A
Operation selection at Digital Operator
interruption
0, 1
1
0
No
n011
010B
01
0B
Maximum frequency (FMAX)
50.0 to
400.0
0.1 Hz
60.0
No
n012
010C
01
0C
Maximum voltage (VMAX)
0.1 to
255.0
[0.1 to
510.0]
0.1 V
200.0
[400.0]
No
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...