Chapter 10
10-18
Appendices
01
06
Drive Mode
Set to parameter n002/A1-
02. Some Inverters do not
support the setting.
00: Open loop vector
([n002/A1-02] = 2)
01: V/f control ([n002/A1-
02] = 0)
02: V/f control with PG (A1-
02 = 1)
03: Flux vector control (A1-
02 = 3)
After changing the setting,
the power must be turned
OFF and then ON again to
enable the new setting.
00 to 03
3G3MV:
01
3G3RV:
01
3G3FV:
00
Yes
Yes
Byte
07
Speed Actual
Rotational
Speed Monitor
(See notes 2
and 4.)
The output frequency moni-
tor (U-02/U1-02) can be
monitored in hexadecimal
with the minimum unit as 1.
The frequency monitor’s
minimum unit can be set by
the frequency reference
setting and display units in
n035/o1-03.
n035/o1-03 = 0: 0.01 Hz
n035/o1-03 = 1: 0.01%
(100%: Max. frequency.)
n035/o1-03 = 2 to 39:
1 r/min
n035/o1-03 = 40 to 3,999:
Follow individual set values.
When r/min units are being
used, a multiplier can be set
in attribute 16 (the Speed
Scale setting).
---
0000
Yes
No
Word
08
Speed Refer-
ence
Rotational
Speed Refer-
ence
(See notes 2
and 4.)
Can be set and read in
hexadecimal with the fre-
quency reference minimum
unit as 1.
The frequency reference
minimum unit can be set by
the frequency reference
setting and display units in
n035/o1-03.
n035/o1-03 = 0: 0.01 Hz
n035/o1-03 = 1: 0.01%
(100%: Max. frequency.)
n035/o1-03 = 2 to 39:
1 r/min
n035/o1-03 = 40 to 3,999:
Follow individual set values.
When r/min units are being
used, a multiplier can be set
in attribute 16 (the Speed
Scale setting).
0 to max. fre-
quency
0000
Yes
Yes
Word
09
Current Actual
Can be referenced in hexa-
decimal with the output cur-
rent monitor U-03/U1-03
minimum unit as 0.1 A.
Setting the attribute 17 cur-
rent scale enables a multi-
plication factor to be set.
---
0000
Yes
No
Word
Instance
Attribute
Name
Content
Setting range
Default
Read Write
Size
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...