Chapter 10
10-13
Appendices
■
Object Details
10-2-8 Motor Data Objects: Class 28 Hex
Motor data objects are data and functions related to motors connected to Inverters. The motors that
can be connected to Inverters are squirrel-cage inductive motors, so the “Motor Type” is always “7."
The motor's rated current and rated voltage can be set and read.
■
Support Service Code
Instance
Attribute
Name
Content
Setting range
Default
Read Write
Size
00
01
Object Software
Revision
Indicates the software revi-
sion of Class 08.
The revision value increases
when changes have been
made.
---
0001
Yes
No
Word
02
Max Instance
Indicates the number of out-
put terminals. (Depends on
the Inverter being used.)
---
0003
Yes
No
Word
01 to 03
(One per
terminal)
03
Value
Terminal status
00: OFF, 01: ON
---
00
Yes
No
Byte
05
Fault Action
Hold/clear output after fault
00: Hold, 01: Clear
00, 01
00
Yes
Yes
Byte
65
Lifetime mode
selection
Maintenance count method
00: Conduction time,
01: Number of ON operations
00, 01
00
Yes
Yes
Byte
66
Lifetime present
value
Present value of the mainte-
nance count
---
0000
0000
Yes
Yes
Reset
Long
67
Lifetime monitor
flag
Maintenance count compari-
son result
(ON when PV
≥
threshold)
00: OFF, 01:ON
---
00
Yes
No
Byte
68
Lifetime thresh-
old setting
Lifetime monitor value
Set the cumulative time that
the output is ON (s) or the
number of contact opera-
tions.
0000 0000 to
FFFF FFFF
0000
0000
Yes
Yes
Long
Service code number (hex)
Service
0E
Get attribute single
10
Set attribute single
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...