Chapter 5
5-8
Remote I/O Functions
9.Click the
I/O Allocation (IN)
Tab and display the
Edit I/O Allocate
Window.
In the
Poll
settings, set
Block: 1
and
Allocated: 3300
(user-set).
In the
COS
settings, set
Block: 2
and
Allocated: 3500
(user-set).
10.Set the
I/O Allocation (OUT)
settings in the same way.
Set
Block: 1
and
Allocated: 3200
(user-set).
11.Return to the
General
Tab Page and click the
Download
Button.
12.When the download has been completed, restart with the new settings.
Reference
• When
Auto allocation as is registered
is selected on the Master’s
General
Tab Page, a message will
appear every time that connection path settings are changed. The message will indicate that the
present I/O allocation was cleared because the connection was changed. When making connection
path settings, clear the
Auto allocation as is registered
check box before registering the Slaves.
• When connection settings are changed, a warning mark may be displayed by the Inverter Slave’s
icon. In this case, click the
Get I/O Size from the Scan List
Button on the
I/O Information
Tab Page
of the Inverter Slave’s
Property
Window and edit the information so that the I/O information for the
Slave’s icon matches the Master’s scan list. (For details, refer to
7-1-3 Network Connection Precau-
tions
.)
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...