Chapter 9
9-19
Communications Programs (CS-series PLCs)
9-3-2 Reading Parameter Data
This programming example is designed to read the parameter data specified in the 3G3MV Inverter.
To use special remote I/O, it is necessary to switch the remote I/O operation. Refer to
5-2 Switching
the Remote I/O Function
and change to the special remote I/O operation.
■
Allocation
●
Remote I/O Allocation Areas
■
Timing Chart
I/O classification
Word address
15 to 8
7 to 0
Output
(PLC to 3G3MV
Inverter)
n
Register number (leftmost
byte)
Function code (10: Write, 03:
Read)
n+1
Register data (leftmost byte)
Register number (rightmost
byte)
n+2
Not used.
Register data (rightmost byte)
Input
(3G3MV Inverter to
PLC)
m
Register number (leftmost
byte)
Function code (10: Write, 03:
Read)
m+1
Register data (leftmost byte)
Register number (rightmost
byte)
m+2
Not used.
Register data (rightmost byte)
Bit
000000
Bit
000002
Bit
003000
Bit
003001
Bit
003005
D00000
D00001
Flag
Input
Read Parameter Input Bit
Faulty Data Reset Input Bit
Data Read Flag
Faulty Data Flag
Data Read Completed Flag
Register number of the parameter to be read
Read data
1
2
000000 (Read Parameter
Input Bit)
003000 (Data Read Flag)
003005 (Data Read Completed
Flag)
Word n to n+2 (Send Data)
Word m to m+2 (Receive Data)
Send Data (Read)
Receive Data (Read)
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...