Chapter 4
4-11
SYSDRIVE Inverter Settings
4-3-2 Inverter Operation Command Selection
• Select the method for inputting Run and Stop Commands to the Inverter. Select the method suit-
able for the application.
• When operation commands (forward, reverse, stop) from the DeviceNet communications are to be
always used, set to 3."
■
Switching of Operation Commands from DeviceNet Communications
There is a switching signal, “Net. Ctrl.,” for operation commands from the standard remote I/O of the
DeviceNet Communications Card. This function cannot be used with the 3G3FV.
When it is necessary to select the operation command from DeviceNet communications, change the
setting in parameter b1-02 with an explicit message (Class 64 hex, Instance 01 hex, Attribute 04
hex).
4-3-3 DeviceNet Communications Settings
The parameters below are for functions that are exclusive to DeviceNet communications. Set these
parameters according to the desired application.
Parameter
No.
Set value
Contents
Default
setting
b1-02
0
Digital Operator
Operation commands from the Digital
Operator
1
External termi-
nals
Control circuit terminals (sequence input)
2
Not used (Do not set.)
3
Optional Card
Operation commands using DeviceNet
Communications Card
Parameter
No.
Name
Contents
Setting
range
Default
setting
Operator display
F9-01
Communications external fault
input: input type
Select the type of input used for the
communications external fault input
from communications (DeviceNet
Communications Card).
0: N.O. input (external fault
detected when 1)
1: N.C. input (external fault
detected when 0)
0, 1
0
EFO Selection
F9-02
Communications external fault
input: detection method
Select the detection method used
for the communications external
fault input from communications
(DeviceNet Communications
Card).
0: Always detect.
1: Detect during operation (i.e.,
when operation commands are
input).
0, 1
0
EFO Detection
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...