Chapter 10
10-66
Appendices
10-6 3G3PV Register Numbers, Classes, Instances, and
Attributes
10-6-1 Inputting Control/Frequency (Read/Write)
Note
Set all unused bits to 0.
Class 64
Register No.
(Hex)
Contents
In-
stance
At-
tribute
---
---
0000
Reserved
00
01
0001
Frequency reference
Bit 0
Run/stop command
1: Run 0: Stop
Bit 1
Reverse/stop command 1: Reverse 0: Stop
Bit 2
Multi-function input command 3
Bit 3
Multi-function input command 4
Bit 4
Multi-function input command 5
Bit 5
Multi-function input command 6
Bit 6
Multi-function input command 7
Bit 7
Not used.
Bit 8
External error
1: Error (EFO)
Bit 9
Error reset
1: Reset command
Bits 10 to 15
Not used.
00
02
0002
Frequency reference (Set units using parameter o1-03.)
---
---
0003 to 0005
Not used.
00
06
0006
PID target value
00
07
0007
Analog output 1 setting (
−
11 V/
−
726 Dec. to 11 V/726 Dec.)
00
08
0008
Not used.
00
09
0009
Multi-function contact output setting
Bit 0
Contact output (terminal M1-M2) 1: ON 0: OFF
Bit 1
Contact output (terminal M3-M4) 1: ON 0: OFF
Bits 2 to 5
Not used.
Bit 6
Set error contact (terminal MA-MC) output using bit 7.
1: ON 0: OFF
Bit 7
Error contact (terminal MA-MC)
1: ON 0: OFF
Bits 8 to 15
Not used.
---
---
000A to 000E Not used.
00
0F
000F
Reference selection settings
Bit 0
Not used.
Bit 1
PID target value (register 0006H) 1: Enabled 0: Disabled
Bits 2 to 15
Not used.
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...