![background image](http://html1.mh-extra.com/html/omron/3g3mv-pdrt2/3g3mv-pdrt2_user-manual_743559068.webp)
Chapter 3
3-16
Setup and Wiring
Align the cable connector with the socket on the T-branch Tap as shown in the following diagram and
fully insert the connector into the socket. Tighten the set screws to secure the connection. Tighten
the screws to a torque of 0.3 N·m.
Note
To avoid damaging the cable or breaking wires, do not pull on the cable or bend it too sharply
when connecting it to the T-branch Tap. Also, never place heavy objects on top of the cable.
3-2-4 Connecting Terminating Resistors
Terminating resistors must be connected at each end of the trunk line. Use the methods described
here to connect the Terminating Resistors.
●
T-branch Tap Terminating Resistor
A Terminating Resistor is included with the T-branch Tap. Insert the Terminating Resistor into the T-
branch Tap as shown in the following diagram. The Terminating Resistor can face in either direction.
●
Terminal-block Terminating Resistor
A Terminating Resistor is built into the Terminal-block Terminating Resistor. To connect the cable to
the Terminating Resistor, attach standard M3 crimp terminals to the signal wires and securely screw
the terminals to the Terminal-block Terminating Resistor. Tighten to a torque of 0.5 N·m.
41 max.
21 max.
20 max.
DRS1-T
20
Model
DRS1-T
Specifications
121
Ω±
1%, 1/4W
Manufacturer
OMRON
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...