Chapter 10
10-62
Appendices
L2-06
048A
04
8A
KEB deceleration time
0.0 to
200.0
0.1 s
0.0
No
L2-07
048B
04
8B
Momentary recovery time
0.0 to
25.5
0.1 s
0.0 (See
note 2.)
No
L2-08
048C
04
8C
Frequency reduction gain at KEB start
0 to 300
1
100
No
L3-01
048F
04
8F
Stall prevention selection during accel
0 to 2
1
1
No
L3-02
0490
04
90
Stall prevention level during accel
0 to 200
1%
120 (See
note 3.)
No
L3-03
0491
04
91
Stall prevention limit during accel
0 to 100
1%
50
No
L3-04
0492
04
92
Stall prevention selection during decel
0 to 3
1
1
No
L3-05
0493
04
93
Stall prevention selection during run-
ning
0 to 2
1
1
No
L3-06
0494
04
94
Stall prevention level during running
30 to 200 1%
120 (See
note 3.)
No
L4-01
0499
04
99
Speed agreement detection level
0.0 to
400.0
0.1 Hz
0.0
No
L4-02
049A
04
9A
Speed agreement detection width
0.0 to
20.0
0.1 Hz
2.0
No
L4-03
049B
04
9B
Speed agreement detection level (+/
−
)
−
400.0 to
400.0
0.1 Hz
0.0
No
L4-04
049C
04
9C
Speed agreement detection width (+/
−
) 0.0 to
20.0
0.1 Hz
2.0
No
L4-05
049D
04
9D
Operation when frequency reference is
lost
0, 1
1
0
No
L4-06
04C2
04
C2
Frequency reference for loss of fre-
quency reference
0.0 to
100.0
0.1%
80.0
No
L5-01
049E
04
9E
Number of auto restart attempts
0 to 10
1
0
No
L5-02
049F
04
9F
Auto restart operation selection
0, 1
1
0
No
L6-01
04A1
04
A1
Torque detection selection 1
0 to 8
1
0
No
L6-02
04A2
04
A2
Torque detection level 1
0 to 300
1%
150
No
L6-03
04A3
04
A3
Torque detection time 1
0.0 to
10.0
0.1 s
0.1
No
L6-04
04A4
04
A4
Torque detection selection 2
0 to 8
1
0
No
L6-05
04A5
04
A5
Torque detection level 2
0 to 300
1%
150
No
L6-06
04A6
04
A6
Torque detection time 2
0.0 to
10.0
0.1 s
0.1
No
L7-01
04A7
04
A7
Forward drive torque limit
0 to 300
1%
200
No
L7-02
04A8
04
A8
Reverse drive torque limit
0 to 300
1%
200
No
L7-03
04A9
04
A9
Forward regenerative torque limit
0 to 300
1%
200
No
L7-04
04AA
04
AA
Reverse regenerative torque limit
0 to 300
1%
200
No
L8-01
04AD
04
AD
Protect selection for internal DB resis-
tor
0, 1
1
0
No
L8-02
04AE
04
AE
Overheat pre-alarm level
50 to 130 1
°
C
Depends
on
capacity.
No
L8-03
04AF
04
AF
Operation selection after overheat pre-
alarm
0 to 3
1
3
No
L8-05
04B1
04
B1
Input open-phase protection selection
0, 1
1
1 (0)
(See
note 4.)
No
L8-07
04B3
04
B3
Output open-phase protection selec-
tion
0, 1
1
0
No
L8-09
04B5
04
B5
Ground protection selection
0, 1
1
1
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...