Chapter 5
5-12
Remote I/O Functions
5-4
Standard Remote I/O
Standard remote I/O is the factory setting for the DeviceNet Communications Unit/Card.
General Inverter control can be performed with this remote I/O function.
■
I/O Format (Allocated Words)
●
Outputs (PLC to Inverter)
Instance ID: 21 Decimal (15 Hex)
●
Inputs (Inverter to PLC)
Instance ID: 71 Decimal (47 Hex)
Note
A shaded box indicates that the bit is not used.
■
Bit and Data Functions
●
Output Bit Details
Byte number
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Wd n
Right-
most
0
Net Ref-
erence
Net Con-
trol
Fault
Reset
Reverse/
stop
Forward/
stop
Left-
most
1
Wd n+1
Right-
most
2
Rotational speed reference (rightmost data)
Left-
most
3
Rotational speed reference (leftmost data)
Byte number
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Wd m
Right-
most
0
At Refer-
ence
Refer-
ence
From Net
Control
From Net
Inverter
Ready
During
reverse
run
During
forward
run
Alarm
Fault
Left-
most
1
Wd m+1
Right-
most
2
Rotational speed monitor (rightmost data)
Left-
most
3
Rotational speed monitor (leftmost data)
Name
Function
Forward/stop
0: Stop, 1: Forward
Reverse/stop
0: Stop, 1: Reverse
Fault Reset
0: ---, 1: Fault reset
Net Control
0: Specified in n003/b1-02, 1: Device Net
(See notes 1 and 2.)
Net Reference
0: Specified in n004/b1-01, 1: Device Net
(See notes 1 and 3.)
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...