Chapter 2
2-14
Example System Startup
■
Example IN Area and OUT Area
The following diagram shows the IN and OUT Area allocations for this Chapter’s example system
configuration when fixed I/O allocation is used for remote I/O communications.
When shipped, the Inverter’s default communications setting is “Standard Remote I/O”, so the follow-
ing functions are allocated to the node 3 Inverter.
●
Outputs (PLC to Inverter)
●
Inputs (Inverter to PLC)
Note
A shaded box indicates that the bit is not used.
Byte number
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Wd 3203 Right-
most
0
Net Ref-
erence
Net Con-
trol
Fault
Reset
Reverse/
stop
Forward/
stop
Left-
most
1
Wd 3204 Right-
most
2
Rotational speed reference (rightmost data)
Left-
most
3
Rotational speed reference (leftmost data)
Byte number
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Wd 3303 Right-
most
0
At Refer-
ence
Refer-
ence
From Net
Control
From Net
Inverter
Ready
During
reverse
run
During
forward
run
Alarm
(minor
fault)
Fault
Left-
most
1
Wd 3304 Right-
most
2
Rotational speed monitor (rightmost data)
Left-
most
3
Rotational speed monitor (leftmost data)
IN Area
Fixed allocation
OUT Area
3200
3201
3202
3300
3301
3302
3303
3304
3304
3304
3304
3304
3304
(Node 0)
Node 1
Node 2
Node 3
(Node 4)
Node 5
(Node 6)
(Node 7)
(Node 8)
(Node 9)
Not used
Not used
Not used
DRT2-ID16 (node 1)
DRT2-OD16 (node 2)
3203
3204
3G3MV-PDRT2
(node 3)
3205
3206
DRT2-OD16 (node 5)
3G3MV-PDRT2
(node 3)
Not used
3207
Not used
3208
Not used
3209
Not used
Not used
Not used
Not used
Not used
Not used
Not used
XWT-OD08
Word
Word
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...