Chapter 5
5-4
Remote I/O Functions
■
Setting with an Explicit Message
The remote I/O function can also be switched by sending an explicit message.
If the DeviceNet Configurator is used, the settings are easier to perform because of the customized
settings windows, but in some cases explicit messages may be preferred. Refer to C
hapter 6 Mes-
sage Communications
and
10-2 Objects
for details.
Example
The default connection path can be changed by setting one of the following values for Class 94 hex,
Instance 01 hex, Attribute 64 hex and then resetting the power supply.
Data
Default connection path
0
Basic I/O
1
Standard I/O
2
Special I/O
3
Extended Control I/O
4
Extended Control I/O + Unit status
5
Extended Control I/O + Multi-function Input Monitor