Chapter 10
10-92
Appendices
■
Application Parameters
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
b1-01
0180
01
03
Frequency reference selection
0 to 3
1
1
No
b1-02
0181
01
04
Run source selection
0 to 3
1
1
No
b1-03
0182
01
05
Stopping method selection
0 to 3
1
0
No
b1-04
0183
01
06
Disabling reverse operation
0, 1
1
0
No
b1-05
0184
01
07
Operation selection for minimum fre-
quency (E1-09 or less)
0 to 3
1
0
No
b1-06
0185
---
---
Setting control input responsiveness
0, 1
1
1
No
b1-07
0186
---
---
Operation selection after switching to
remote mode
0, 1
1
0
No
b1-08
01A6
---
---
Run source selection when not in drive
mode
0, 1
1
0
No
b2-01
0187
01
08
Excitation level (DC injection starting
frequency)
0.0 to
10.0
0.1 Hz
0.5
No
b2-02
0188
01
09
DC injection braking current
0 to 100
1%
50
No
b2-03
0189
01
0A
DC injection braking time at start
0.00 to
10.00
0.01 s
0.00
No
b2-04
018A
01
0B
DC injection braking time at stop
0.00 to
10.00
0.01 s
0.50
No
b2-08
01AB
---
---
Magnetic flux compensation amount
0 to 500
1%
0
No
b3-01
018E
01
0C
Speed search selection at start
0, 1
1
0 (See
note.)
No
b3-02
018F
01
0D
Speed search operation current
0 to 200
1%
100
No
b3-03
0190
01
0E
Speed search deceleration time
0.1 to
10.0
0.1 s
2.0
No
b4-01
0192
---
---
Timer function ON-delay time
0.0 to
300.0
0.1 s
0.0
No
b4-02
0193
---
---
Timer function OFF-delay time
0.0 to
300.0
0.1 s
0.0
No
b5-01
0194
01
0F
PID control selection
0 to 4
1
0
No
b5-02
0195
01
10
Proportional gain (P)
0.00 to
25.00
0.01
1.00
Yes
b5-03
0196
01
11
Integral time (I)
0.0 to
360.0
0.1 s
1.0
Yes
b5-04
0197
01
12
Integral limit (I)
0.0 to
100.0
0.1%
100.0
Yes
b5-05
0198
01
13
Differential time (D)
0.00 to
10.00
0.01 s
0.00
Yes
b5-06
0199
01
14
PID limit
0.0 to
100.0
0.1%
100.0
Yes
b5-07
019A
01
15
PID offset adjustment
−
100.0 to
100.0
0.1%
0.0
Yes
b5-08
019B
01
16
PID primary delay time constant
0.00 to
10.00
0.01 s
0.00
Yes
b5-09
01A7
---
---
PID output characteristic selection
0, 1
1
0
No
b5-10
01A8
---
---
PID output gain
0.0 to
25.0
0.1
1.0
No
b5-11
01A9
---
---
PID output reverse selection
0, 1
1
0
No
b5-12
01AF
---
---
Feedback loss detection selection
0 to 2
1
0
No
b5-13
01B0
---
---
Feedback loss detection level
0 to 100
1%
0
No
b5-14
01B1
---
---
Feedback loss detection time
0.0 to
25.0
0.1 s
1.00
No
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...