Chapter 10
10-48
Appendices
00
61
0061
OPE error
parameter
Monitors U1-34; outputs parameter
00
63
0063
PID input
quantity
Monitors U1-36; 0.01% units (max. frequency =
100%; with sign)
00
64
0064
PID output
quantity
Monitors U1-37; 0.01% units (max. frequency =
100%; with sign)
00
65
0065
PID reference
Monitors U1-38; 0.01% units (max. frequency =
100%)
00
66
0066
RS-422A/485
communica-
tions error
Monitors U1-39
Bit 0
CRC error
Bit 1
Invalid data length
Bit 2
Not used.
Bit 3
Parity error
Bit 4
Overrun error
Bit 5
Framing error
Bit 6
Time-out
Bit 7 to
15
Not used.
00
68
0068
Fan operating
time
Monitors U1-40; 1-hr units
00
80
0080
Current fault
Monitors U2-01
Code
Error
dis-
play
Code
Error
dis-
play
Code
Error
dis-
play
01
PUF
0E
OL4
1C
LF
02
UV1
0F
RR
1D
OH3
03
UV2
10
RH
1E
OPR
04
UV3
11
EF3
1F
ERR
06
GF
12
EF4
20
OH4
07
OC
13
EF5
22
BUS
08
OV
14
EF6
25
CF
09
OH
15
EF7
27
EF0
0A
OH1
18
OS
28
FBL
0B
OL1
19
DEV
29
UL3
0C
OL2
1A
PGO
2A
UL4
0D
OL3
1B
PF
2B
OL7
00
81
0081
Last fault
Monitors U2-02 (same codes as U2-01)
00
82
0082
Fault fre-
quency refer-
ence
Monitors U2-03; 0.01-Hz units (units set in o1-03;
with sign)
00
83
0083
Fault output
reference
Monitors U2-04; 0.01-Hz units (units set in o1-03;
with sign)
00
84
0084
Fault output
current
Monitors U2-05; 0.1-A units
00
85
0085
Fault motor
speed
Monitors U2-06; 0.01-Hz units (units set in o1-03;
with sign)
Class 64
Register
number (hex)
Content
Instance
Attribute
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...