![background image](http://html1.mh-extra.com/html/omron/3g3mv-pdrt2/3g3mv-pdrt2_user-manual_743559352.webp)
Chapter 10
10-94
Appendices
Note 1.
The setting range and setting unit for acceleration/deceleration times will differ according to
the setting for C1-10 (the unit for acceleration/deceleration time). If C1-10 is set to 0, the set-
ting range for acceleration/deceleration times is 0.00 to 600.00 (s).
Note 2.
When the control mode is changed, the Inverter will revert to default settings. (The open loop
vector control default settings are given above.)
C3-03
0211
01
30
Slip compensation limit.
0 to 250
1%
200
No
C3-04
0212
01
31
Slip compensation during regeneration. 0, 1
1
0
No
C3-05
0242
01
32
Flux Calculation Method
0, 1
1
0
No
C3-06
0243
---
---
Output voltage limiting action selection
0, 1
1
0
No
C4-01
0213
01
33
Torque compensation gain.
0.00 to
2.50
0.01
1.00
Yes
C4-02
0214
01
34
Torque compensation delay time.
0 to
10000
1 ms
20 (See
note 2.)
No
C4-03
0244
---
---
Startup torque (forward operation)
0.0 to
200.0
0.1%
0.0
No
C4-04
0245
---
---
Startup torque (reverse operation)
−
200.0 to
0.0
0.1%
0.0
No
C4-05
0246
---
---
Startup torque compensation time
0 to 200
1 ms
10
No
C5-01
0215
01
35
ASR Proportional (P) gain 1
0.00 to
300.00
0.01
20.00
(See
note 2.)
Yes
C5-02
0216
01
36
ASR Integral (I) time 1
0.000 to
10.000
0.001 s
0.500
(See
note 2.)
Yes
C5-03
0217
01
37
ASR Proportional Gain (P) 2
0.00 to
300.00
0.01
20.00
(See
note 2.)
Yes
C5-04
0218
01
38
ASR Integral (I) time 2
0.000 to
10.000
0.001 s
0.500
(See
note 2.)
Yes
C5-05
0219
01
39
ASR Limit
0.0 to
20.0
0.1%
5.0
No
C5-06
021A
01
3A
ASR Primary delay time
0.000 o
0.500
0.001 s
0.004
No
C5-07
021B
01
3B
ASR Switching frequency
0.0 to
400.0
0.1 Hz
0.0
No
C5-08
0241
01
3C
ASR Integral (I) Limit
0 to 400
1%
400
No
C6-01
021C
01
3D
Carrier frequency upper limit.
2.0 to
15.0
(See
note 4.)
0.1 kHz
15.0
(See
note 3.)
No
C6-02
021D
01
3E
Carrier frequency lower limit.
0.4 to
15.0
0.1 kHz
15.0
(See
note 3.)
No
C6-03
021E
01
3F
Carrier frequency proportional gain.
0 to 99
1
0
No
C7-01
021F
01
40
Hunting prevention selection
0, 1
1
1
No
C7-02
0220
01
41
Hunting prevention gain
0.00 to
2.50
0.01
1.00
No
C8-08
022A
01
42
AFR Gain
0.00 to
10.00
0.01
1.00
No
C8-09
022B
---
---
AFR primary delay time
0 to 2000 1 ms
50
No
C8-30
0240
---
---
Carrier Frequency Selection during
Auto-tuning
1 to 2
1
2
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...