![background image](http://html1.mh-extra.com/html/omron/3g3mv-pdrt2/3g3mv-pdrt2_user-manual_743559296.webp)
Chapter 10
10-38
Appendices
■
Function Group 3 (n080 to n119)
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
n080
0150
01
50
Carrier frequency selection
1 to 4, 7
to 9
1
Differs
with
capacity.
No
n081
0151
01
51
Momentary power interruption com-
pensation
0 to 2
1
0
No
n082
0152
01
52
Number of fault retries
0 to 10
1
0
No
n083
0153
01
53
Jump frequency 1
0.00 to
400.0
0.01 Hz
0.00
No
n084
0154
01
54
Jump frequency 2
0.00 to
400.0
0.01 Hz
0.00
No
n085
0155
01
55
Jump frequency 3
0.00 to
400.0
0.01 Hz
0.00
No
n086
0156
01
56
Jump width
0.00 to
25.50
0.01 Hz
0.00
No
n087
0157
01
57
Cumulative operation time selection
0, 1
1
0
No
n088
0158
01
58
Cumulative operation time
0 to 6550 1
(10 h)
0
No
n089
0159
01
59
DC injection braking current
0 to 100
1%
50
No
n090
015A
01
5A
DC injection braking-to-stop time
0.0 to
25.5
0.1 s
0.5
No
n091
015B
01
5B
Startup DC injection braking time
0.0 to
25.5
0.1 s
0.0
No
n092
015C
01
5C
Stall prevention during deceleration
0, 1
1
0
No
n093
015D
01
5D
Stall prevention level during accelera-
tion
30 to 200 1%
170
No
n094
015E
01
5E
Stall prevention level during operation
30 to 200 1%
160
No
n095
015F
01
5F
Frequency detection level
0.00 to
400.0
0.01 Hz
0.00
No
n096
0160
01
60
Overtorque detection function selection
1
0 to 4
1
0
No
n097
0161
01
61
Overtorque detection function selection
2
0, 1
1
0
No
n098
0162
01
62
Overtorque detection level
30 to 200 1%
160
No
n099
0163
01
63
Overtorque detection time
0.1 to
10.0
0.1 s
0.1
No
n100
0164
01
64
UP/DOWN frequency selection
0, 1
1
0
No
n101
0165
01
65
Speed search deceleration time
0.0 to
10.0
0.1 s
2.0
No
n102
0166
01
66
Speed search level
0 to 200
1%
150
No
n103
0167
01
67
Torque compensation gain
0.0 to 2.5 0.1
1.0
Yes
n104
0168
01
68
Torque compensation primary delay
time constant
0.0 to
25.5
0.1 s
0.3
No
n105
0169
01
69
Torque compensation core loss
0.0 to
6550
0.1 W
Differs
with
capacity.
No
n106
016A
01
6A
Rated motor slip
0.0 to
20.0
0.1 Hz
Differs
with
capacity.
Yes
n107
016B
01
6B
Motor phase-to-neutral resistance
0.000 to
65.50
0.001
Ω
Differs
with
capacity.
No
Summary of Contents for 3G3MV-PDRT2
Page 4: ......
Page 12: ......
Page 36: ...Chapter 1 1 22 Functions and System Configuration...
Page 52: ...Chapter 2 2 16 Example System Startup...
Page 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Page 130: ...Chapter 5 5 36 Remote I O Functions...
Page 234: ...Chapter 8 8 14 Communications Errors...
Page 362: ...R 2 Revision History...