Chapter 5 Parameters
158
P173
Encoder outputs B pulse phase
Range
Default
value
Unit
Usag
e
0
~
1
0
ALL
The meaning of this parameter are
0: in-phase
1: anti-phase
This parameter can adjust the phase relation between B phase signal and A phase signal.
That is, when motor CCW, A phase lags B phase 90 degree (P173=0) or A phase advances B
phase 90 degree (P173=1); when motor CW, A phase advances B phase 90 degree (P173=0)
or A phase lags B phase 90 degree (P173=1).
P174
Encoder outputs Z pulse phase
Range
Default
value
Unit
Usag
e
0
~
1
0
ALL
The meaning of this parameter are
0: in-phase
1: anti-phase
P175
Encoder outputs Z pulse width
Range
Default
value
Unit
Usag
e
0
~
15
0
ALL
The meaning of this parameter are
0: Pass-through, which is the original width of encoder Z signal.
1~15: the width is double width of parameter value multiplying output signal A (or B)
Broaden Z pulse. When the upper device can not catch narrow Z pulse, it can be widened.
But you had better use Z pulse front edge.
P178
Trigger mode of homing
Range
Default
value
Unit
Usag
e
0
~
3
0
ALL
The meanings of this parameter are:
0
:
The homing function is closed.
1
:
Level triggering by the input GOH of DI
2
:
Rising edge triggering by the input GOH of DI
Summary of Contents for EP3 AC Series
Page 1: ...Wuhan Maxsine Electric Co Ltd...
Page 12: ...Chapter 1 Product inspection and installment 2 1 2 Product nameplate...
Page 16: ...Chapter 1 Product inspection and installment 6...
Page 40: ...Chapter 2 Wiring 30 2 5 2 Wiring diagram for speed or torque control...
Page 57: ...3 7 Resume the parameter default values 47 Remarks...
Page 124: ...Chapter 4 Running 114 Remarks...
Page 221: ...198 Chapter 8 Specifications 8 1 Types of servo driver...
Page 231: ...8 5 Types of servo motor 8 5 Types of servo motor...