Chapter 4 Parameters
4-67
When Pr.02.05 is set to 1 or 3, it does not guarantee that the motor will never run under this
condition. It is possible the motor may be set in motion by a malfunctioning switch.
Related parameters: Pr.02.01(Source of First Operation Command)
02.06
Loss of ACI Signal (4-20mA)
Factory Setting: 1
Settings
0
Decelerate
to
0Hz
1
Coast to stop and display “AErr”
2
Continue operation by the last frequency command
This parameter determines the behavior when ACI is lost.
When setting to 1, it will display warning message “AErr” on the keypad(optional) in case of
loss of ACI signal and execute the setting. The AC motor drive will stop outputting immediately,
the motor will free run to stop. Please press “RESET” key to clear it.
When setting 0 or 2, it will not display warning message “AErr” on the keypad(optional) in case
of loss of ACI signal and execute the setting. If it is set to 0, the motor will decelerate to 0Hz by
the setting of deceleration time (Pr.01.10/Pr.01.12). If it is set to 2, the motor will continue to
run. For these two settings, the warning message will stop blinking when ACI signal is
recovered. Please press “RESET” key to clear it.
Related parameters: Pr.01.10(Decel Time 1) and Pr.01.12(Decel Time 2)
02.07
Up/Down Mode
Factory Setting: 0
Settings
0
By digital keypad up/down keys mode
1
Based on Accel/Decel Time acc. to Pr.01.09 to 01.12
2
Constant speed (acc. to Pr. 02.08)
3
Pulse input unit (acc. to Pr. 02.08)
This parameter determines the increase/decrease of the master frequency when operated via
the Multi-function Inputs when Pr.04.05~Pr.04.08 are set to 10 (Up command) or 11 (Down
command).