D-35
Special
M
Function
Read(R)/
Write(W)
M1025 RUN(ON) / STOP(OFF) the AC motor drive
R/W
M1026 Setting operation direction of the AC motor drive (0: FWD, 1:REV)
R/W
M1027 Trigger motor drive reset
R/W
M1028 Enable(ON)/disable(OFF)
high-speed counter function
R/W
M1029 Clear the value of high-speed counter
R/W
M1030 Decide to count up(OFF)/count down(ON)
R/W
M1031
Enforce setting current integral value of PID equal to D1019 (activate from 0
to 1)
R/W