Chapter 4 Parameters
4-163
Group 12: Analog Input/Output Parameters for Extension Card
Make sure that the extension card is installed on the AC motor drive correctly before using group 12
parameters. See Appendix B for details.
12.00
AI1 Function Selection
Factory Setting: 0
Settings
0
Disabled
1
Source of the 1st frequency
2
Source of the 2nd frequency
3
PID Set Point (PID enable)
4
Positive
PID
feedback
5
Negative
PID
feedback
12.01
AI1 Analog Signal Mode
Factory Setting: 1
Settings
0
ACI2 analog current (0.0 ~ 20.0mA)
1
AVI3 analog voltage (0.0 ~ 10.0V)
Besides parameters settings, the voltage/current mode should be used with the switch.
AVI3
ACI2
AVI4
ACI3
AVO1
ACO1
AVO2
ACO2
12.02
Min. AVI3 Input Voltage
Unit: V
Settings
0.0 to 10.0V
Factory Setting: 0.0
12.03
Min. AVI3 Scale Percentage
Unit: %
Settings
0.0 to 100.0%
Factory Setting: 0.0
12.04
Max. AVI3 Input Voltage
Unit: V
Settings
0.0 to 10.0V
Factory Setting: 10.0