Chapter 4 Parameters
4-78
03.02
Desired Frequency 1 Attained
Unit: 0.01
03.14
Desired Frequency 2 Attained
Unit: 0.01
Settings
0.00 to 599.00 Hz
Factory Setting: 0.00
If a multi-function output terminal is set to function as Desired Frequency Attained 1(Pr.03.00
to Pr.03.01=09), then the output will be activated when the output frequency reaches Pr.03.02
setting.
If a multi-function output terminal is set to function as Desired Frequency Attained 2(Pr.03.00
to Pr.03.01=23), then the output will be activated when the output frequency reaches Pr.03.14
setting.
Related parameters: Pr.03.00(Multi-function Output Relay (RA1, RB1, RC1)) and
Pr.03.01(Multi-function Output Terminal MO1)
-2Hz
4Hz
2Hz
OF F
OF F
ON
ON
OF F
ON
OF F
ON
OF F
OF F
ON
OF F
ON
ON
detec ti on
range
F requenc y
master
frequency
desir ed
frequency
03.02/03.14
detec ti on range
detec ti on
range
DC brak e time
during stop
Time
waiting time
for
frequency
run/stop
setting 2
master freq. attained
(output signal)
setting 9/23
desir ed freq. attai ned
setting 03 z ero s peed indication
setting 19 z ero s peed indication
ou tp ut t im ing ch art of m ultip le fu nct io n term inals(Pr.03.00/Pr.03.01)
wh en settin g to fr eq uen cy att ained or zero sp eed in dicatio n
NOTE
When the output frequency reaches the setting frequency, the detection ranges for the multi-function
output terminals are:
±
2Hz (from OFF to ON) and
±
4Hz (from ON to OFF). The detection range for
the output frequency reaches the desired frequency is -2Hz.
03.03
Analog Output Signal (AFM)
Factory Setting: 0
Settings
0
Analog Frequency Meter (0 to Maximum Output Frequency)
1
Analog Current Meter (0 to 250% of rated AC motor drive current)
This parameter sets the function of the AFM output 0~+10VDC (ACM is common). Refer to
Pr.03.04 for applications.
Related parameters: Pr.01.00(Maximum Output Frequency (Fmax)) and Pr.03.04(Analog
Output Gain)