D-37
Special D
Function
Read(R)/ Write(W)
D1023-
D1024
Reserved --
D1025 The present value of the high-speed counter C235 (low byte)
R
D1026 The present value of the high-speed counter C235 (high byte)
R
D1027 Frequency command of the PID control
R
D1028
The value of AVI (analog voltage input) 0-10V corresponds to 0-
1023
R
D1029
The value of ACI (analog current input) 4-20mA corresponds to 0-
1023 or the value of AVI2 (analog voltage input) 0-10V
corresponds to 0-1023
R
D1030 The value of V.R digital keypad 0-10V corresponds to 0-1023
R
D1031
Extension card AI1 analog input: 0~10V or 0~20mA correspond to
(0~4095)
R
D1032
Extension card AI2 analog input: 0~10V or 0~20mA correspond to
(0~4095)
R
D1033-
D1035
--
--
D1036 Motor Drive fault code
R
D1037-
D1039
--
--
D1040 AFM analog output value
R/W
D1041
Extension card AO1 analog output:
0~10V or 0~20mA correspond to (0~65535), bit status of M1010 is
disabled.
0~10V or 0~20mA correspond to (0~10000), bit status of M1010 is
enabled.
R/W
D1042
Extension card AO2 analog output:
0~10V or 0~20mA correspond to (0~65535), bit status of M1010
is disabled.
0~10V or 0~20mA correspond to (0~10000), bit status of M1010 is
enabled.
R/W
D1043
User defined (when Pr.00.04 is set to 2, the register data will be
displayed as C xxx)
R/W
D1044 High-speed
counter
mode
R/W