Chapter 4 Parameters
4-4
Group 1 Basic Parameters
Parameter Explanation
Settings
Factory
Setting
Customer
01.00
Maximum Output
Frequency (Fmax)
50.00 to 599.00 Hz
60.00
01.01
Maximum Voltage
Frequency (Fbase)
(Motor 0)
0.10 to 599.00 Hz
60.00
01.02
Maximum Output
Voltage (Vmax)
(Motor 0)
115V/230V series: 0.1V to 255.0V
220.0
460V series: 0.1V to 510.0V
440.0
01.03
Mid-Point Frequency
(Fmid) (Motor 0)
0.10 to 599.00 Hz
1.50
01.04
Mid-Point Voltage
(Vmid) (Motor 0)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
01.05
Minimum Output
Frequency (Fmin)
(Motor 0)
0.10 to 599.00 Hz
1.50
01.06
Minimum Output
Voltage (Vmin)
(Motor 0)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
01.07
Output Frequency
Upper Limit
0.1 to 120.0%
110.0
01.08
Output Frequency
Lower Limit
0.0 to100.0 %
0.0
01.09
Accel Time 1
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.10
Decel Time 1
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.11
Accel Time 2
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.12
Decel Time 2
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.13 Jog
Acceleration
Time
0.1 to 600.0 / 0.01 to 600.0 sec
1.0
01.14 Jog
Deceleration
Time
0.1 to 600.0 / 0.01 to 600.0 sec
1.0
01.15
Jog Frequency
0.10 Hz to 599.00 Hz
6.00
01.16
Auto acceleration /
0: Linear Accel/Decel
0