Chapter 4 Parameters
4-65
02.04
Motor Direction Control
Factory Setting: 0
Settings
0
Forward/Reverse operation enabled
1
Reverse
operation
disabled
2
Forward
operation
disabled
This parameter is used to disable one direction of rotation of the AC motor drive direction of
rotation to prevent damage due to operation faults.
The motor direction also can be limited by setting one of Pr.04.05~04.08 to 21.
Related parameters: Pr.04.05(Multi-function Input Terminal (MI3)), Pr.04.06(Multi-function
Input Terminal (MI4)), Pr. 04.07(Multi-function Input Terminal (MI5)) and Pr.04.08(Multi-
function Input Terminal (MI6))
Rotating reversely command
from the motor drive
Rotating forward command
from the motor drive
Rotating direction of the motor
Counter-clockwisely
02.05
The source of Power-On command and Running command modifies the operating
control of the VFD
Settings
Factory Setting: 1
0:
Start running when Power is on.
1:
Don’t run when Power is on
2:
When the source of the command changes, VFD’s operation remains
the same.
3:
4:
When the source of the command changes, VFD’s operation follows the
new command.
The motor drive can start to run at power on or after reset.
When the source of command is a 2-wire external terminal, the
operating command changes as the external terminal’s status changes.
This parameter determines the response of the drive upon power on and operation command
source is changed.
Pr.02.05
Start lockout (Run when power is ON)
Operation status when operation
command source is changed
0
Disable (AC motor drive will run)
Keep previous status
1
Enable (AC motor drive doesn’t run)
Keep previous status
2
Disable (AC motor drive will run)
Change according to the new
operation command source