B.12 KPC-CC01 keypad
Due to VFD-E
default communication protocol is ASCII 9600, 7, N, 2, but KPC-CC01 communication
protocol is RTU 19200, 8, N, 2, you need to set VFD-E
communication parameters so that it can
connect with
KPC-CC01. Set Pr.09.00=1, 09.01=2, 09.04=3 and you can select operating functions by
pressing KPC-CC01 MENU key. Please refer to CH.4 Pr.09 Group for details.
Pr.09.00 Communication Address
Pr.09.01 Transmission Speed (Baud rate)
Pr.09.04 Communication Protocol
KPC-CC01 is communicating with control board by using 255 communication station, so if the
Transmission Speed is corresponding with Communication Protocol, the control board can receive
packet properly
,
it can judge as keypad devices and communicate mutually.
Digital Keypad only can support
the serial production after product series No.: xxxExxAxT205xxxx,
xxxExxAxW202xxxx.
Some parameters cannot be copied by using PU06, KPC-CC01 or VFDSoft, please refer to B-5 Digital
Keypad PU06 for details.
Descriptions of Digital Keypad
KPC-CC01
Communication Interface:
RJ-45 (socket)
、
RS-485 interface
Installation:
Embedded, it can flat the control box
surface and front waterproof.
You can select optional model:
MKC-KPPK, the protection level is IP56;
user can choose wall mounting or
embedded mounting.