Chapter 4 Parameters
4-2
4.1 Summary of Parameter Settings
: The parameter can be set during operation.
Group 0 User Parameters
Parameter Explanation
Settings
Factory
Setting
Customer
00.00
Identity Code of the
AC motor drive
Read-only ##
00.01 Rated
Current
Display of the AC
motor drive
Read-only
#.#
00.02 Parameter
Reset
0: Parameter can be read/written
0
1: All parameters are read only
6: Clear PLC program (NOT for VFD*E*C
models)
8: keypad lock
9: All parameters are reset to factory settings
(50Hz, 230V/400V or 220V/380V depends on
Pr.00.12)
10: All parameters are reset to factory
settings (60Hz, 220V/440V)
00.03
Start-up Display
Selection
0: Display the frequency command value
(Fxxx)
0
1: Display the actual output frequency (Hxxx)
2: Display the content of user-defined unit
(Axxx)
3: Multifunction display, see Pr.00.04 (Uxxx)
4: FWD/REV command
5: PLCx (PLC selections: PLC0/PLC1/PLC2)
(NOT for VFD*E*C models)
00.04
Content of Multi-
function Display
0: Display the content of user-defined unit
(Uxxx)
0
1: Display the counter value (c)
2: Display PLC D1043 value (C) (NOT for
VFD*E*C models)
3: Display DC-BUS voltage (u)