Chapter 4 Parameters
4-69
OFF
ON
ON
Frequency
frequency
command
by Pr.02.08 setting
Time
multi-function input
set to 10 (UP command)
Related parameters: Pr.02.08(Accel/Decel Rate of Change of UP/DOWN Operation with
Constant Speed), Pr.04.05(Multi-function Input Terminal (MI3)), Pr.04.06(Multi-function Input
Terminal (MI4)), Pr.04.07(Multi-function Input Terminal (MI5)), Pr.04.08(Multi-function Input
Terminal (MI6))
02.08
Accel/Decel Rate of Change of UP/DOWN Operation with
Constant Speed
Unit: Hz/2ms
Settings
0.01~10.00 Hz/2ms
Factory Setting: 0.01
This parameter determinates the constant speed When Pr.02.08 is set to 2 or 3.
02.11
Keypad Frequency Command
Unit: Hz
Settings
0.00 to 599.00Hz
Factory Setting: 60.00
This parameter can be used to set frequency command or read keypad frequency command.
Related parameters: Pr.02.12 (Communication Frequency Command)
02.12
Communication Frequency Command
Unit: Hz
Settings
0.00 to 599.00Hz
Factory Setting: 60.00
This parameter can be used to set frequency command or read communication frequency
command.
It can use this parameter for remote control via communication.
02.13
The Selections for Saving Keypad or Communication Frequency Command
Factory Setting: 0
Settings
0
Save Keypad & Communication Frequency
1
Save Keypad Frequency only
2
Save Communication Frequency only (Not for VFD*E*C model)
This parameter is used to save keypad or RS-485 frequency command.