Chapter 4 Parameters
4-60
01.40
Mid-Point Frequency (Fmid) (Motor 3)
Unit: Hz
Settings 0.10 to 599.00Hz
Factory Setting: 1.50
01.41
Mid-Point Voltage (Vmid) (Motor 3)
Unit: V
Settings 115V/230V series 0.1 to 255.0V
Factory Setting: 10.0
460V series
0.1 to 510.0V
Factory Setting: 20.0
01.42
Minimum Output Frequency (Fmin) (Motor 3)
Unit: Hz
Settings
0.10 to 599.00Hz
Factory Setting: 1.50
01.43
Minimum Output Voltage (Vmin) (Motor 3)
Unit: V
Settings
115V/230V series 0.1 to 255.0V
Factory Setting: 10.0
460V series
0.1 to 510.0V
Factory Setting: 20.0
The V/f curve of motor 0 to motor 3 can be selected by setting the multi-function input
terminals MI3~MI6 (Pr.04.05 to Pr.04.08) to 27 and 28. To set the voltage and frequency for
each motor, please refer to Pr.01.01~01.06 for motor 0 (factory setting), Pr.01.26~01.31 for
motor 1, Pr.01.32~01.37 for motor 2 and Pr.01.38~01.43 for motor 3.
Related parameters: Pr.04.05(Multi-function Input Terminal (MI3)), Pr.04.06(Multi-function
Input Terminal (MI4)), Pr.04.07(Multi-function Input Terminal (MI5)) and Pr.04.08(Multi-function
Input Terminal (MI6))