Chapter 2 Installation & Wiring
2-19
2.4 Control Terminals
Circuit diagram for digital inputs (NPN current 16mA.)
+24
NPN Mode
multi-input
terminal
Internal Circuit
DCM
+24V
Multi-Input
Terminal
DCM
Internal Circuit
PNP Mode
The position of the control terminals
RS-485
10V
MI1 MI2 MI3 MI4 MI5 MI6
DCM
24V
DCM
ACM
AVI ACI
AFM MCM MO1
RA
RB
RC
Terminal symbols and functions
Terminal
Symbol
Terminal Function
Factory Settings (NPN mode)
ON: Connect to DCM
MI1 Forward-Stop
command
ON:
Run in MI1 direction
OFF:
Stop acc. to Stop Method
MI2 Reverse-Stop
command
ON:
Run in MI2 direction
OFF:
Stop acc. to Stop Method
MI3 Multi-function
Input
3
Refer to Pr.04.05 to Pr.04.08 for programming the
Multi-function Inputs.
ON: the activation current is 6mA.
OFF: leakage current tolerance is 10
μ
A.
MI4 Multi-function
Input
4
MI5 Multi-function
Input
5
MI6 Multi-function
Input
6
+24V
DC Voltage Source
+24VDC, 120mA used for PNP mode.