Chapter 4 Parameters
4-55
01.13
Jog Acceleration Time
Unit: second
Settings
0.1 to 600.0/0.01 to 600.0 sec
Factory Setting: 1.0
01.14
Jog Deceleration Time
Unit: second
Settings
0.1 to 600.0/0.01 to 600.0 sec
Factory Setting: 1.0
01.15
Jog Frequency
Unit: Hz
Settings
0.10 to 599.00Hz
Factory Setting: 6.00
Only external terminal JOG (MI3 to MI12) can be used. Please set one of MI3~MI12
(MI7~MI12 are optional) to 8 for JOG operation. When the Jog command is “ON”, the AC
motor drive will accelerate from Minimum Output Frequency (Pr.01.05) to Jog Frequency
(Pr.01.15). When the Jog command is “OFF”, the AC motor drive will decelerate from Jog
Frequency to zero.
The used Accel/Decel time is set by the Jog Accel/Decel time (Pr.01.13, Pr.01.14).
Before using the JOG command, the drive must be stopped first. And during Jog operation,
other operation commands are not accepted, except commands via the FORWARD,
REVERSE and STOP keys on the digital keypad.
01.13
01.12
01.21
Frequency
Time
JOG Accel. Time
JOG Decel. Time
The definition of JOG Accel./Decel. Time
01.15
JOG
Frequency
Min. output
frequency
01.05
0 Hz
01.14
01.16
Auto-Acceleration / Deceleration
Factory Setting: 0
Settings
0
Linear acceleration / deceleration
1
Auto acceleration, linear Deceleration.
2
Linear acceleration, auto Deceleration.
3
Auto acceleration / deceleration (set by load)
4
Auto acceleration / deceleration (set by Accel/Decel Time setting)
5
Linear Accel. controlled by current, linear Decel.
6
Linear Accel. controlled by current, auto Decel.
Linear acceleration/deceleration: the acceleration/deceleration that acts according to the
acceleration/deceleration time set by Pr.01.09~01.12.